Chint NXB-40
🔍

Chint

NXB-40 Miniature Circuit Breaker

NXB-40 Miniature Circuit Breaker is designed for overload and short-circuit protection in low-voltage distribution systems. It is suitable for residential, commercial, and industrial applications. The product complies with GB/T 10963.1 and IEC 60898-1 standards and supports rated currents from 6A to 40A.

Brand
Chint
Model
NXB-40
Product category
Circuit Breaker

Product overview

The NXB-40 series Miniature Circuit Breaker is a protection device designed for low-voltage terminal distribution systems. It is mainly used for overload protection and short-circuit protection of electrical circuits. The product complies with **GB/T 10963.1 and IEC 60898-1 international standards** and has obtained **CCC and CE certifications**, providing reliable electrical performance and safety protection. The NXB-40 series offers multiple rated current options including **6A, 10A, 16A, 20A, 25A, 32A, and 40A**. It supports **C and D tripping characteristics** to meet different load requirements and application scenarios. With a compact structure design, the product supports **1P+N pole configuration**. It provides a mechanical endurance of up to **20,000 operations** and an electrical endurance of **10,000 operations**. The rated short-circuit breaking capacity reaches **4500A**, ensuring safe and reliable operation of low-voltage distribution systems. NXB-40 is widely used in residential distribution boxes, commercial buildings, industrial control cabinets, lighting circuits, and power circuit protection applications.

Specifications

Parameter Specification Unit
Product Model NXB-40 -
Product Type Miniature Circuit Breaker (MCB) -
Applicable Standard GB/T 10963.1, IEC 60898-1 -
Certification CCC, CE -
Main Function Overload protection, Short-circuit protection -
Rated Current (In) 6A, 10A, 16A, 20A, 25A, 32A, 40A A
Rated Operating Voltage (Ue) 230 V
Rated Insulation Voltage (Ui) 500 V
Rated Frequency 50 Hz
Instantaneous Tripping Characteristic C, D -
Number of Poles 1P+N -
Mechanical Endurance 20000 Operations
Electrical Endurance 10000 Operations
Rated Short-Circuit Breaking Capacity (Icn) 4500 A
Service Short-Circuit Breaking Capacity (Ics) 4500 A
Rated Impulse Withstand Voltage (Uimp) 4 kV
Maximum Power Loss Per Pole
Rated Current In(A) Maximum Power Loss (W)
6-10A 2
16-25A 3.5
32-40A 5
Derating Factor for Multiple Devices Installed Side by Side
Number of Devices Installed Together Derating Factor
≤3 devices 0.90-0.95In
4-6 devices 0.80-0.86In
7-9 devices 0.76-0.78In
≥9 devices 0.76In
Altitude Correction Factor
Altitude Correction Factor
≤2000m In
3000m 0.96In
4000m 0.94In
5000m 0.90In
Application Areas
  • Residential low-voltage distribution systems
  • Commercial building power distribution
  • Industrial control cabinets
  • Lighting circuit protection
  • Power circuit protection
  • Low-voltage distribution boxes