Acti9 C120L-S miniature circuit breakers are designed for high-power load applications, providing high-current load protection and control, overload and short-circuit protection for distribution circuits, as well as manual switching and isolation functions. They can be used with Vigi C120 residual current protection accessories.
Acti9 C120L-S miniature circuit breakers are modular low-voltage protection devices designed for high-power load applications.
The products provide high-current load protection and control, distribution circuit overload protection, short-circuit protection, as well as manual switching and isolation functions. They can be used together with Vigi C120 residual current protection accessories to provide enhanced protection capabilities for low-voltage distribution systems.
Acti9 C120L-S supports C curve and D curve tripping characteristics, with a rated current range of 63A~125A. The rated operating voltage reaches up to 400V AC, and the rated breaking capacity reaches 15000A, making it suitable for commercial buildings, industrial distribution systems and high-load terminal circuits.
The product adopts DIN 35 mm standard rail mounting and supports flexible installation direction from 0° to 360°. The device provides IP20 protection degree, and can reach IP40 when installed in Pragma or Prisma distribution enclosures.
Acti9 C120L-S complies with GB10963.1 and IEC60898-1 standards, providing a reliable protection solution for high-load low-voltage distribution systems.
Specifications
Technical Parameters
Product Features
Parameter
Specification
Product Type
C120L-S Miniature Circuit Breaker
Application
High-power load applications
Main Functions
High-current load protection and control, overload protection, short-circuit protection, manual switching and isolation
Tripping Curve
C Curve / D Curve
Compatible Accessories
Vigi C120 residual current protection accessories
Installation Method
DIN 35 mm standard rail mounting
Installation Direction
Flexible 0°~360° installation
Compliance Standards
Standard
GB10963.1
IEC60898-1
Electrical Parameters
Parameter
Value
AC Operating Frequency
50/60 Hz
Number of Poles
1P / 2P / 3P / 4P
Rated Current In
63A~125A
Rated Operating Voltage Ue (1P)
230V AC
Rated Operating Voltage Ue (2P, 3P, 4P)
400V AC
Rated Breaking Capacity Icn
15000A
Wiring Parameters
Parameter
Value
Flexible Wire
1.5~35 mm²
Solid Wire
1~50 mm²
Tightening Torque
3.5 N·m
Technical Characteristics
Parameter
Value
Maximum Operating Voltage
440V AC
Rated Insulation Voltage Ui
500V
Rated Impulse Withstand Voltage Uimp
4kV
Current Limiting Class
3
Pollution Degree
3
Positive Contact Indication
Yes
Rapid Tripping Function
Yes
Thermal Release Reference Temperature
30°C
Magnetic Release C Curve
5~10 In
Magnetic Release D Curve
10~14 In
Protection Parameters
Parameter
Value
Protection Degree (Device)
IP20
Protection Degree (Installed in Pragma or Prisma Enclosure)
IP40
Insulation Class
Class II
Service Life
Parameter
Value
Electrical Endurance (63A)
10000 operations
Electrical Endurance (80~125A)
5000 operations
Mechanical Endurance
20000 operations
Environmental Parameters
Parameter
Value
Operating Temperature Range
-40°C~+70°C
Storage Temperature Range
-40°C~+80°C
Hook Quantity
Number of Poles
Quantity
1P / 2P
1 piece
3P / 4P
2 pieces
Weight
Type
Weight
C120L-S 1P
205 g
C120L-S 2P
410 g
C120L-S 3P
615 g
C120L-S 4P
820 g