Schneider Electric Acti9 Pro iC65N Miniature Circuit Breaker, B/C/D Curve
Schneider Electric Acti9 Pro iC65N miniature circuit breaker for AC 50/60Hz low-voltage distribution systems, providing short-circuit protection, overload protection, isolation function, fault trip indication, and B/C/D tripping curves
The Schneider Electric Acti9 Pro iC65N miniature circuit breaker is designed for AC 50/60Hz low-voltage distribution systems. It provides short-circuit protection, overload protection and isolation control for electrical circuits. The product complies with GB/T10963.1 and IEC 60898-1 standards, and features clear fault trip indication. The front window displays a red indicator when the circuit breaker trips due to a fault.
The iC65N series supports B, C and D tripping curves, allowing selection according to different load types. The rated current range is 1–80A, the rated voltage is up to 500V AC, and the rated short-circuit breaking capacity is 6000A. It is suitable for residential, commercial, industrial and terminal distribution applications.
The product can be mounted on a 35mm standard DIN rail, with flexible installation orientation from 0° to 360°. The circuit breaker body has an IP20 protection rating, and can reach IP40 when installed inside a distribution enclosure. It also offers reliable mechanical and electrical endurance
- Short-circuit protection
- Overload protection
- Isolation function
- Clear fault trip indication
- Red fault indication window on the front
- 35mm standard DIN rail mounting
- Flexible 0°–360° installation orientation
Specifications
Certifications and Standards
Item
Description
Standard
GB/T10963.1
International Standard
IEC 60898-1
Certification Marks
CCC, CE, CB
Wiring Parameters
Rated Current
Screw Size
Rated Torque
Limit Torque
National Standard Rated Torque
Copper Solid Wire
Copper Flexible Wire or Ferruled Terminal
1–32A
M5
2.5 N·m
5.1 N·m
2 N·m
1–25 mm²
1–16 mm²
40–80A
M6.5
3.5 N·m
5.6 N·m
3.5 N·m
1–35 mm²
1–25 mm²
Basic Technical Parameters
Parameter
Specification
Insulation Voltage Ui
500 V AC
Pollution Degree
3
Rated Impulse Withstand Voltage Uimp
4 kV
Reference Calibration Temperature
30°C
B Curve Tripping Range
3–5 In
C Curve Tripping Range
5–10 In
D Curve Tripping Range
10–14 In
Utilization Category
A
Current Limiting Class
3
Single-Pole Breaking Capacity Icn1
Icn1 = Icn 6000A
Breaking Capacity Parameters
System Type
Operating Voltage Ue
Rated Current In
Rated Breaking Capacity Icn
Service Breaking Capacity Ics
Ph/Ph, 2/3/4P
400V
1–80A
6000A
100%
Ph/N, 1P
230V
1–80A
6000A
100%
Installation and Operating Parameters
Parameter
Specification
Mounting Rail
DIN 35mm standard rail
Installation Orientation
0°–360°
Stripping Length
14 mm
Tool Type
PZ2
Reference Dimension
6.5 mm
Protection Rating of Circuit Breaker Body
IP20
Protection Rating Inside Distribution Enclosure
IP40
Insulation Class
II
Electrical Endurance
10,000 cycles
Mechanical Endurance
20,000 cycles
Overvoltage Category IEC/EN 60364
IV
Operating Ambient Temperature
-40°C to +70°C
Storage Ambient Temperature
-40°C to +85°C
Damp Heat Resistance IEC/EN 60068-1
Class 2, relative humidity 95% at 55°C
Padlock Quantity for 1P/2P
1
Padlock Quantity for 3P/4P
2
Weight Parameters
Poles
Average Weight
1P
115 g
2P
229 g
3P
342 g
4P
457 g