Schneider Electric Acti9 Pro iDPNa miniature circuit breaker for overload protection, short-circuit protection and control of terminal circuits. It can disconnect both phase and neutral conductors, with isolation protection and fault trip indication
Schneider Electric Acti9 Pro iDPNa miniature circuit breaker is designed for terminal distribution circuits, providing overload protection, short-circuit protection and circuit control. The product can disconnect both the phase conductor and neutral conductor at the same time, while the neutral conductor does not provide protection. It is suitable for low-voltage distribution applications in residential buildings, commercial buildings and terminal distribution boxes.
The product complies with GB/T10963.1 and IEC/EN 60898-1 standards. It provides isolation protection, clear fault trip indication, and a red front window to indicate fault tripping status. The product supports 1P+N pole configuration, with a rated current range of 6–40A, operating voltage of 230V, breaking capacity of 4500A, and service breaking capacity Ics of 100%.
The product can be mounted on a 35mm standard DIN rail and supports flexible installation from 0° to 360°. The circuit breaker body has an IP20 protection rating, and can reach IP40 when installed inside a distribution box. It provides stable electrical and mechanical endurance.
- Overload protection
- Short-circuit protection
- Isolation protection
- Circuit control
- Disconnects both phase and neutral conductors
- Clear fault trip indication
- Red front window indicating fault trip status
- 35mm standard DIN rail mounting
- Flexible 0°–360° installation orientation
Specifications
Certifications and Standards
Item
Description
National Standard
GB/T10963.1
International Standard
IEC/EN 60898-1
Certification Marks
CCC, CE
Environmental Label
Green Premium
Breaking Capacity Parameters
Poles
Operating Voltage Ue
Rated Current In
Breaking Capacity Icn
Service Breaking Capacity Ics
Ph/N, 1P+N
230V
6–40A
4500A
100%
Wiring Parameters
Screw Size
Rated Torque
Limit Torque
Copper Solid Wire
Copper Flexible Wire or Ferruled Terminal
M4.2
2 N·m
3.5 N·m
1–16 mm²
1–16 mm²
Main Technical Parameters
Parameter
Specification
Insulation Voltage Ui
400 V AC
Pollution Degree
2
Rated Impulse Withstand Voltage Uimp
4 kV
Reference Setting Temperature
30°C
C Curve Tripping Range
5–10 In
D Curve Tripping Range
10–14 In
Utilization Category
A
Current Limiting Class
3
Other Parameters
Parameter
Specification
Mounting Rail
DIN 35mm standard rail
Installation Orientation
0°–360°
Stripping Length
14 mm
Tool Type
PZ2
Reference Dimension
5.5 mm
Protection Rating, Circuit Breaker Body
IP20
Protection Rating, Installed in Distribution Box
IP40
Insulation Class
II
Electrical Endurance
>20A: 10,000 cycles; ≤20A: 20,000 cycles
Mechanical Endurance
20,000 cycles
Overvoltage Category IEC/EN 60364
II
Operating Ambient Temperature
-25°C to +60°C
Storage Ambient Temperature
-40°C to +80°C
Damp Heat Resistance IEC/EN 60068-1
Class 2, relative humidity 95% at 55°C
Weight Parameters
Type
Weight
iDPNa 1P+N
122 g